For each door that is attached to this controller, a door monitor can be used. A common type of door monitor is a magnet sensor. The door monitor senses if the door is open or closed and has two purposes:
A door monitor can be used. A common type of door monitor is a magnet sensor. The door monitor senses if the door is open or closed and has two purposes:


* A ''door open too long'' alert will be generated if the door is open too long (configurable for each door).
* A ''door open too long'' alert will be generated if the door is open too long (configurable for each door).
* A "door forced open" alert will be generated if the door is opened without a prior ''access granted'' event, such as presenting a valid credential to the reader or using the REX button (see below).
* A "door forced open" alert will be generated if the door is opened without a prior ''access granted'' event, such as presenting a valid credential to the reader or using the REX button (see below).


There are two monitor inputs; one on socket DOOR IN 1 and one on DOOR IN 2.


[[File:A9161_monitor_settings.png|Monitor settings]]

[[File:monitor_settings.png|Monitor settings]]





Revision as of 10:42, 5 July 2019

Door

The A9161 controller can control one door:


Door


Select the door from the dropdown list (you may need to create it first).

Lock settings

The A9161 controller has only one relay to control a lock. Specify which door it belongs to by using the dropdown list.


Lock settings


It is also necessary to specify whether it should be configured as fail-safe or fail-secure:

  • Fail-secure means that the door is locked if the power fails (it is secure from intruders on the outside). This is the default.
  • Fail-safe means that the door is unlocked if the power fails (it is safe for people on the inside, e.g. in the event of a fire).

Monitor settings

A door monitor can be used. A common type of door monitor is a magnet sensor. The door monitor senses if the door is open or closed and has two purposes:

  • A door open too long alert will be generated if the door is open too long (configurable for each door).
  • A "door forced open" alert will be generated if the door is opened without a prior access granted event, such as presenting a valid credential to the reader or using the REX button (see below).


Monitor settings


Make the connection between monitor input and door by using the dropdown list. Also specify if an open circuit means that the door is open or closed. The default is open circuit = open door.

Reader settings

Maximum two readers can be attached to the A1001 controller (or one if a hub is used). Possible combinations include:

  • One door and one reader
  • Two doors and one reader each
  • One door with two readers (one for each direction)
  • No readers at all (if only credentials of type Remote are used)


Reader settings


Make the connection between reader socket and door by using the dropdown list.

Also specify the type of reader. Supported reader types are:

  • RS485 half duplex OSDP
  • Wiegand single LED
  • Wiegand double LED

REX settings

REX (Request to EXit) devices are inputs that trigger by either opening or closing a circuit. A typical REX device is an "open button" that unlocks (or more exactly; grants access to) the door from the inside. Maximum two REX devices can be attached to an A1001 controller.


REX settings


Make the connection between REX device and door by using the dropdown list and specify whether opening or closing the circuit should trigger the request to exit.

A special case of using a REX device / input is where a user opens the door manually and the door has a door monitor. Normally, this will trigger the door forced open alert, but this may not be the desired behavior. In this case, it is possible to use a specific REX device that will trigger as soon as the door starts to open and configure it as either Closing circuit allows or Opening circuit allows. The effect of this is to prevent the door forced open alert to be generated.

Pin chart

After saving or editing the settings for an A1001 controller, Telcred Access Manager can generate a pin chart that summarizes the physical connections on the controller. The pin chart is accessed by clicking the link in the lower right hand corner of the controller detail screen:


Pin chart link


Pin chart